Application
Outdoor or indoor use.
For use with single wire armour ‘W’, wire braid ‘X’, aluminium strip armour ‘Y’ and steel tape armour ‘Z’ elastomer and plastic insulated cables.
For particular use with cables that exhibit ‘cold flow’ characteristics.
Features
Provides armour clamping using one clamping arrangement for all armour/braid types.
Provides a diaphragm seal on the cables inner sheath which will not damage cable that has ‘cold flow’ characteristics.
Provides an outer deluge seal to prevent moisture ingress to the cable armour/braid.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer sheath.
Materials & Finishes
The 153/Universal cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard.
Category: Cable Glands
Product code: R153/Universal
5 stars, based on 1 reviews
CABLE GLAND SELECTION TABLE | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Size Ref. |
Entry Thread Size |
Thread Length ‘H’ |
Cable Acceptance Details |
‘G’ Compressed Length |
Hexagon Dimensions |
||||||||
Inner Sheath ‘A’ |
Outer Sheath ‘B’ |
‘C’ Armour/Braid |
|||||||||||
Metric |
NPT * |
Across Flats |
Across Corners |
||||||||||
Standard | Option | Min. | Max. | Min. | Max. |
Orientation 1 |
Orientation 2 |
||||||
Os | M20 ‡ | ½" | - | 15 | 3.5 | 8.1 | 5.5 | 12.0 | 0.8 / 1.25 | 0 / 0.8 | 61.6 | 24.0 | 26.5 |
O | M20 ‡ | ½" | - | 15 | 6.5 | 11.5 | 9.5 | 16.0 | 0.8 / 1.25 | 0 / 0.8 | 61.6 | 24.0 | 26.5 |
A | M20 | ¾" | ½" | 15 | 8.4 | 14.3 | 12.5 | 20.5 | 0.8 / 1.25 | 0 / 0.8 | 63.0 | 30.0 | 32.5 |
B | M25 | 1" | ¾" | 15 | 11.1 | 19.7 | 16.9 | 26.0 | 1.25 / 1.6 | 0 / 0.7 | 69.9 | 36.0 | 39.5 |
C | M32 | 1¼" | 1" | 15 | 17.6 | 26.5 | 22.0 | 33.0 | 1.6 / 2.0 | 0 / 0.7 | 73.2 | 46.0 | 50.5 |
C2 | M40 | 1½" | 1¼" | 15 | 23.1 | 32.5 | 28.0 | 41.0 | 1.6 / 2.0 | 0 / 0.7 | 77.9 | 55.0 | 60.6 |
D | M50 | 2" | 1½" | 15 | 28.9 | 44.4/42.3 † | 36.0 | 52.6 | 1.8 / 2.5 | 0 / 1.0 | 93.5 | 65.0 | 70.8 |
E | M63 | 2½" | 2" | 15 | 39.9 | 56.3/54.3 † | 46.0 | 65.3 | 1.8 / 2.5 | 0 / 1.0 | 94.0 | 80.0 | 88.0 |
F | M75 | 3" | 2½" | 15 | 50.5 | 68.2/65.3 † | 57.0 | 78.0 | 1.8 / 2.5 | 0 / 1.0 | 103.0 | 95.0 | 104.0 |
G size and above are available in the 153/RAC design style. | |||||||||||||
G | M80 | 3½" | - | 20 | 67.0 | 73.0 | 75.0 | 89.5 | 2.0 / 3.5 | 0 / 1.0 | 90.6 | 106.4 | 115.0 |
H | M90 | 3½" | - | 20 | 67.0 | 77.6 | 75.0 | 89.5 | 2.0 / 3.5 | 0 / 1.0 | 90.6 | 115.0 | 130.0 |
J | M100 | 4" | - | 20 | 75.0 | 91.6 | 88.0 | 104.5 | 2.5 / 4.0 | 0 / 1.0 | 90.6 | 127.0 | 142.0 |
All dimensions in millimetres (except * where dimensions are in inches). Os - F size metric entry threads are 1.5mm pitch as standard. For G size Cable Glands and above, a 2mm pitch is supplied as standard (1.5mm pitch with 15mm length of thread can be supplied) please specify when ordering. † Smaller value is applicable when selecting reduced NPT entry option. ‡ Sizes Os and O are available with an M16 thread size. For O size with M16 thread, the maximum cable inner sheath diameter is 10.9mm. |