RSS ترمینال باکس استنلس استیل
316 L Stainless Steel.
Category: Stainless Steel Enclosure
Product code: SS9
5 stars, based on 1 reviews
ENCLOSURE DISSIPATED WATTAGE | |||||
---|---|---|---|---|---|
Enclosure Type | Temperature Class | ||||
T6 40°C & T5 55°C | T6 55°C | T5 40°C | T6 65°C | T5 65°C | |
Size 9 Stainless Steel | 79.35 | 49.5 | 109.1 | 29.7 | 59.5 |
MAXIMUM QUANTITY OF ENTRIES PER FACE | |||||||||
---|---|---|---|---|---|---|---|---|---|
Thread Size | M16 | M20/O | M20/A | M25 | M32 | M40 | M50 | M63 | M75 |
Bottom Face C Quantity |
64 # * | 60 | 52 | 42 | 20 | 16 | 8 | 6 | 4 |
Side Faces B & D Quantity |
88 # * | 84 | 68 | 54 | 28 | 22 | 12 | 8 | 6 |
# Serrated washers/locknuts with large outside diameters may foul on adjacent cable glands. * Serrated washers/locknuts must not foul on aperture wall. Entry quantities shown for faces B,C & D are split over two gland plates. |
TERMINAL CAPACITY DATA | ||||||||
---|---|---|---|---|---|---|---|---|
Terminal Type | Conductor Size (mm²) |
Max. Volts |
Max. Physical Terminal Content |
Reduced Terminal Content At Max. Terminal Amps |
||||
Min. | Max. |
Terminal Quantity |
Amps |
Terminal Quantity |
Amps | |||
WDU 2.5 | 0.5 | 2.5 | 550 | 1232 | 2 | 28 | 17 | |
WDU 4 | 0.5 | 4 | 690 | 980 | 3 | 27 | 22 | |
WDU 6 | 0.5 | 6 | 550 | 735 | 5 | 23 | 29 | |
WDU 10 | 1.5 | 10 | 550 | 595 | 7 | 20 | 40 | |
WDU 16 | 1.5 | 16 | 690 | 490 | 10 | 17 | 53 | |
WDU 35 | 2.5 | 35 | 690 | 371 | 16 | 13 | 87 | |
WDU 50 | 6 | 50 | 690 | 308 | 21 | 18 | 88 | |
WDU 70N | 10 | 70 | 690 | 172 | 34 | 11 | 134 | |
WDU 70/95 | 16 | 70 | 690 | 64 | 55 | 10 | 134 | |
WDU 70/95 | 16 | 95 | 690 | 64 | 63 | 14 | 134 | |
WDU 120/150 | 35 | 120 | 690 | 54 | 75 | 11 | 162 | |
WDU 120/150 | 35 | 150 | 690 | 54 | 81 | 13 | 162 | |
WFF 35 | 2.5 | 35 | 1100 | 96 | 34 | 19 | 76 | |
WFF 70 | 2.5 | 70 | 1100 | 81 | 52 | 16 | 134 | |
WFF 120 | 6 | 120 | 1100 | 42 | 94 | 14 | 162 | |
WFF 185 | 10 | 185 | 1100 | 32 | 131 | 10 | 234 | |
WFF 300 | 25 | 300 | 1100 | 32 | 162 | 8 | 316 | |
The enclosure is supplied with an integral internal/external earth stud assembly. The terminals listed are restricted to a minimum operating temperature of -50°C. |