RSS گلند کابل ضدانفجار آرمور دار سرب دار
Application
Outdoor or indoor use.
For use with single wire armour ‘W’, wire braid ‘X’ and steel tape armour ‘Z’ elastomer and plastic insulated cables with a lead inner sheath.
Features
Provides armour clamping using one clamping arrangement for all armour/braid types.
Provides a seal and an electrical bond on the cables lead inner sheath.
Deluge protection option available, contact Hawke Technical Sales for details.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer sheath.
Materials & Finishes
The 501/453/RAC/L cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard.
Category: Cable Glands
Product code: R501/453/RAC/L
5 stars, based on 1 reviews
CABLE GLAND SELECTION TABLE | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Size Ref. |
Entry Thread Size |
Thread Length ‘H’ |
Cable Acceptance Details |
‘G’ Compressed Length |
Hexagon Dimensions |
||||||||||
Inner Lead Sheath ‘A’ |
Outer Sheath ‘B’ |
‘C’ Armour/Braid |
|||||||||||||
Metric |
NPT * |
Standard Seal+Bond |
Alternative Seal+Bond |
||||||||||||
Across Flats |
Across Corners |
||||||||||||||
Standard | Option | Min. | Max. | Min. | Max. | Min. | Max. |
Orientation 1 |
Orientation 2 |
||||||
O | M20 ‡ | ½" | - | 15 | 6.5 | 10.5 | - | - | 9.5 | 16.0 | 0.8 / 1.25 | 0 / 0.8 | 52.0 | 24.0 | 26.5 |
A | M20 | ¾" | ½" | 15 | - | - | 9.0 | 13.4 | 12.5 | 20.5 | 0.8 / 1.25 | 0 / 0.8 | 53.0 | 30.0 | 32.5 |
B | M25 | 1" | ¾" | 15 | 13.0 | 19.0 | 9.5 | 15.4 | 16.9 | 26.0 | 1.25 / 1.6 | 0 / 0.7 | 59.5 | 36.0 | 39.5 |
C | M32 | 1¼" | 1" | 15 | 19.5 | 25.0 | 15.5 | 21.2 | 22.0 | 33.0 | 1.6 / 2.0 | 0 / 0.7 | 64.0 | 46.0 | 50.5 |
C2 | M40 | 1½" | 1¼" | 15 | 25.0 | 31.2 | 22.0 | 28.0 | 28.0 | 41.0 | 1.6 / 2.0 | 0 / 0.7 | 68.3 | 55.0 | 60.6 |
D | M50 | 2" | 1½" | 15 | 31.5 | 42.3/42.8 † | 27.5 | 34.8 | 34.8 | 52.6 | 1.8 / 2.5 | 0 / 1.0 | 79.0 | 65.0 | 70.8 |
E | M63 | 2½" | 2" | 15 | 42.5 | 53.3/54.5 † | 39.0 | 46.5 | 46.5 | 65.3 | 1.8 / 2.5 | 0 / 1.0 | 78.4 | 80.0 | 88.0 |
F | M75 | 3" | 2½" | 15 | 54.5 | 66.0/64.3 † | 49.5 | 58.3 | 57.0 | 78.0 | 1.8 / 2.5 | 0 / 1.0 | 83.7 | 95.0 | 104.0 |
G | M80 | 3½" | - | 20 | 67.0 | 70.0 | - | - | 75.0 | 89.5 | 2.0 / 3.5 | 0 / 1.0 | 95.6 | 106.4 | 115.0 |
H | M90 | 3½" | - | 20 | 67.0 | 75.0 | - | - | 75.0 | 89.5 | 2.0 / 3.5 | 0 / 1.0 | 95.6 | 115.0 | 130.0 |
J | M100 | 4" | - | 20 | 77.0 | 89.5 | - | - | 88.0 | 104.5 | 2.5 / 4.0 | 0 / 1.0 | 95.6 | 127.0 | 142.0 |
All dimensions in millimetres (except * where dimensions are in inches). O - F size metric entry threads are 1.5mm pitch as standard. For G size Cable Glands and above, a 2mm pitch is supplied as standard (1.5mm pitch with 15mm length of thread can be supplied) please specify when ordering. † Smaller value is applicable when selecting reduced NPT entry option. ‡ Size O is available with an M16 thread size. For O size with M16 thread, the maximum cable inner sheath diameter is 10.9mm. |