رعد سان، تجهیزات نیروگاهی، نفت، گاز و پتروشیمی

گلند کابل بدون آرمور ضد انفجار R501/421

گلند کابل ضد انفجار بدون آرمور

گلند کابل بدون آرمور ضد انفجار R501/421

RSS گلند کابل ضدانفجار بدون آرمور

Application

The 501/421 cable gland provides a seal on the outer cable sheath and is intended for use on non-armoured elastomer and plastic insulated cables. The cable gland is dual certified Exd and Exe and is suitable for installation in Zone 1 (21) and Zone 2 (22) hazardous areas.

Features

When used in increased safety applications, this cable gland may be used with braided cable where the braid and the cables outer sheath pass into the enclosure. The braid must be suitably terminated inside the enclosure.

Materials & Finishes

The 501/421 cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium. Brass NPT entries are nickel plated as standard.

Category: Cable Glands

Product code: R501/421

5 stars, based on 1 reviews

 

 

CABLE GLAND SELECTION TABLE
Size
Ref.
Entry Thread
Size
Thread
Length
‘H’
Cable Acceptance Details ‘G’
Compressed
Length
Hexagon
Dimensions
Outer Sheath ‘B’
Metric NPT
*
Standard Seal Alternative
(S) Seal
Across
Flats
Across
Corners
Standard Option Min. Max. Min. Max.
2K M16 - - 15.0 3.2 8.0 - - 23.5 19.0 21.2
Os M20 ‡ ½" - 15.0 3.2 8.0 - - 23.8 24.0 26.5
O M20 ‡ ½" - 15.0 6.5 11.9 - - 23.8 24.0 26.5
A M20 ¾" ½" 15.0 10.0 14.3 8.5 13.5 24.8 30.0 32.5
B M25 1" ¾" 15.0 13.0 20.2 9.5 15.4 25.8 36.0 39.5
C M32 1¼" 1" 15.0 19.5 26.5 15.5 21.2 28.2 46.0 50.5
C2 M40 1½" 1¼" 15.0 25.0 32.5 22.0 28.0 29.5 55.0 60.6
D M50 2" 1½" 15.0 31.5 44.4/42.3 † 27.5 34.8 40.4 65.0 70.8
E M63 2½" 2" 15.0 42.5 56.3/54.3 † 39.0 46.5 38.2 80.0 88.0
F M75 3" 2½" 15.0 54.5 68.2/65.3 † 49.5 58.3 40.5 95.0 104.0
G M80 3½" - 20.0 67.0 73.0 - - 41.0 106.4 115.0
H M90 3½" - 20.0 67.0 77.6 - - 41.0 115.0 130.0
J M100 4" - 20.0 75.0 91.6 - - 41.0 127.0 142.0
All dimensions in millimetres (except * where dimensions are in inches).
2K - F size metric entry threads are 1.5mm pitch as standard. For G size Cable Glands and above, a 2mm pitch is supplied as standard (1.5mm pitch with 15mm length of thread can be supplied) please specify when ordering.
†Smaller value is applicable when selecting reduced NPT entry option.
‡ Sizes Os and O are available with an M16 thread size. For O size with M16 thread, the maximum cable outer sheath diameter is 10.9 mm

 